EES-POWER-MIB: View SNMP OID List / Download MIB
VENDOR: VERTIV
Home | MIB: EES-POWER-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
ees | 1.3.6.1.4.1.6302 | |||
global | 1.3.6.1.4.1.6302.2 | |||
powerMIB | 1.3.6.1.4.1.6302.2.1 |
Emerson Energy Systems (EES) Power MIB, revision B. |
||
ident | 1.3.6.1.4.1.6302.2.1.1 | |||
identManufacturer | 1.3.6.1.4.1.6302.2.1.1.1 |
The name of the equipment manufacturer. |
||
identModel | 1.3.6.1.4.1.6302.2.1.1.2 |
The manufacturers model designation of the power system. |
||
identControllerFirmwareVersion | 1.3.6.1.4.1.6302.2.1.1.3 |
The firmware (software) version of the controller. |
||
identName | 1.3.6.1.4.1.6302.2.1.1.4 |
The name of the power plant. This object should be set by the administrator. |
||
system | 1.3.6.1.4.1.6302.2.1.2 | |||
systemStatus | 1.3.6.1.4.1.6302.2.1.2.1 |
Status of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) observation - OA, lowest level of abnormal status (4) warning - A3 (5) minor - MA (6) major - CA, highest level of abnormal status (7) unmanaged (8) restricted (9) testing (10) disabled |
||
systemVoltage | 1.3.6.1.4.1.6302.2.1.2.2 |
System voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value. |
||
systemCurrent | 1.3.6.1.4.1.6302.2.1.2.3 |
System current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value. |
||
systemUsedCapacity | 1.3.6.1.4.1.6302.2.1.2.4 |
Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. |
||
psBattery | 1.3.6.1.4.1.6302.2.1.2.5 | |||
psBatteryVoltage | 1.3.6.1.4.1.6302.2.1.2.5.1 |
Battery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value. |
||
psBatteryCurrent | 1.3.6.1.4.1.6302.2.1.2.5.2 |
Battery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value. |
||
psInput | 1.3.6.1.4.1.6302.2.1.2.6 | |||
psInputLineAVoltage | 1.3.6.1.4.1.6302.2.1.2.6.1 |
The AC line A voltage, stored as mV. The integer 2147483647 represents invalid value. |
||
psInputLineBVoltage | 1.3.6.1.4.1.6302.2.1.2.6.2 |
The AC line B voltage, stored as mV. The integer 2147483647 represents invalid value. |
||
psInputLineCVoltage | 1.3.6.1.4.1.6302.2.1.2.6.3 |
The AC line C voltage, stored as mV. The integer 2147483647 represents invalid value. |
||
psTemperature | 1.3.6.1.4.1.6302.2.1.2.7 | |||
psTemperature1 | 1.3.6.1.4.1.6302.2.1.2.7.1 |
The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value. |
||
psTemperature2 | 1.3.6.1.4.1.6302.2.1.2.7.2 |
The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.. |
||
psStatusCommunication | 1.3.6.1.4.1.6302.2.1.2.8 |
The status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent. |
||
psStatusBatteryMode | 1.3.6.1.4.1.6302.2.1.2.9 |
The status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoostCharging(9), AutoBoostCharging(10), CyclicBoostCharging(11), MasterBoostCharging(12), MasterBateryTesting(13). |
||
psSMNumber | 1.3.6.1.4.1.6302.2.1.2.10 | |||
psSMACNumber | 1.3.6.1.4.1.6302.2.1.2.10.1 |
The number of SM AC module. |
||
psSMBATNumber | 1.3.6.1.4.1.6302.2.1.2.10.2 |
The number of SM BAT module. |
||
psSMIONumber | 1.3.6.1.4.1.6302.2.1.2.10.3 |
The number of SM IO module. |
||
alarmLastTrapNo | 1.3.6.1.4.1.6302.2.1.3 |
The sequence number of last submitted alarm trap, also last row in alarmTrapTable. |
||
alarmTrapTable | 1.3.6.1.4.1.6302.2.1.4 |
Table holding information about the submitted alarm traps. |
||
1.3.6.1.4.1.6302.2.1.4.1 |
An entry (conceptual row) in the alarmTrapTable. |
|||
alarmTrapNo | 1.3.6.1.4.1.6302.2.1.4.1.1 |
The unique sequence number of this alarm trap. |
||
alarmTime | 1.3.6.1.4.1.6302.2.1.4.1.2 |
Date and time when event occured (local time), including timezone if supported by controller. |
||
alarmStatusChange | 1.3.6.1.4.1.6302.2.1.4.1.3 |
The type of alarm change. One of (1) activated (2) deactivated |
||
alarmSeverity | 1.3.6.1.4.1.6302.2.1.4.1.4 |
The severity of the alarm. One of (3) observation - OA, lowest level of alarm severity (4) warning - A3 (5) minor - MA (6) major - CA, highest level of alarm severity |
||
alarmDescription | 1.3.6.1.4.1.6302.2.1.4.1.5 |
Free-text description of alarm. |
||
alarmType | 1.3.6.1.4.1.6302.2.1.4.1.6 |
Alarm type, i.e. an integer specifying the type of alarm. |
||
powerEvents | 1.3.6.1.4.1.6302.2.1.5 | |||
alarmTrap | 1.3.6.1.4.1.6302.2.1.5.1 |
An alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap: * alarmTrapNo - The unique sequence number of this alarm trap. * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmStatusChange - (1) activated or (2) deactivated. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm. |